{"product_id":"lm80146-125-hp-1800-rpm-405t-fr-dp-230-460-vac-3-ph-rigid-base-lincoln-fire-pump","title":"Leeson Electric LM80146, 125 HP, 1800 RPM, 405T FR, DP, 230\/460 Vac, 3 PH, Rigid Base, Lincoln Fire Pump","description":"\u003cp\u003eEngineering Data \u003cbr\u003e\nVolts  230 Volts  460 Volts  190\/380 \u003cbr\u003e\nF.L. Amps  288 F.L. Amps  144 F.L. Amps  282\/141 \u003cbr\u003e\nS. F Amps  330 S. F Amps  165 S. F Amps  320\/160\u003c\/p\u003e \n\n\u003cp\u003e--------------------------------------------------------------------------------\u003cbr\u003e\n \u003cbr\u003e\nRPM  1800 Hertz  60\/50     \u003cbr\u003e\nHP  125 Duty  CONTINUOUS TYPE  TDS \u003cbr\u003e\nKW  93         \u003cbr\u003e\nFrame  405T Serv. Factor  1.15 Phase  3 \u003cbr\u003e\nMax Amb  40 Design  B Code  G \u003cbr\u003e\nInsul Class  F Protection  NOT Therm.Prot.   \u003cbr\u003e\nEff 100%  94.5 Eff 75%   PF  87 \u003cbr\u003e\nUL  NONE  CSA  Yes  Bearing OPE  6313 \u003cbr\u003e\nCC Number  CC004A CE  Yes  Bearing PE  6316 \u003cbr\u003e\nLoad Type   Inverter Type   Speed Range  NONE\u003c\/p\u003e \n\n\u003cp\u003e--------------------------------------------------------------------------------\u003cbr\u003e\n \u003cbr\u003e\nMotor Wt.  1070 LB Enclosure  DP Lubrication  STANDARD \u003cbr\u003e\nNameplate  92237-A-X-CDLM-B-A-X Mounting  RIGID Rotation  REV \u003cbr\u003e\nAssembly   Shaft Dia.   Ext. Diag.  A-EE7308AA-LN  \u003cbr\u003e\nCust Part No   Outline  B-SS509599LN-1700 Ext. Diag2   \u003cbr\u003e\nPackaging  N Outline Dash No   Winding  T4054138 \u003cbr\u003e\nCarton Label       GROUP:  1  \u003cbr\u003e\nIris   Paint  RED ENAMEL Test Card\u003c\/p\u003e   \n\n\u003cp\u003e--------------------------------------------------------------------------------\u003cbr\u003e\n \u003cbr\u003e\nForm Factor   RMS Amps   Const Torque Speed Range   \u003cbr\u003e\nTorque   Peak        \u003cbr\u003e\nAB Code   Peak@DegC       \u003cbr\u003e\nResistance           \u003cbr\u003e\nConnection\u003c\/p\u003e           \n\n\u003cp\u003e--------------------------------------------------------------------------------\u003cbr\u003e\n \u003cbr\u003e\nRework Status    Rework TYPE\u003c\/p\u003e        \n\n\u003cp\u003e--------------------------------------------------------------------------------\u003cbr\u003e\n \u003cbr\u003e\nHazardous Loc NONE Brake Motors   \u003cbr\u003e\nExplosion Proof   Temp Op Code   FORCE   \u003cbr\u003e\nClass   GROUP:   VDC   \u003cbr\u003e\nClass   GROUP:   ADC   \u003cbr\u003e\n        Brake Coil OHMs @25 C   \u003cbr\u003e\nPerformance \u003cbr\u003e\nTorque UOM   Inertia (WK²)        \u003cbr\u003e\nTorque         \u003cbr\u003e\nCURRENT (amps)         \u003cbr\u003e\nEfficiency (%)         \u003cbr\u003e\nPowerFactor         \u003cbr\u003e\nLoad Curve Data @60\/50 Hz, 460 Volts, 125 Horsepower  \u003cbr\u003e\nLoad Amps KW  RPM  Torque  Eff PF  Rise By Resis Frame Rise \u003cbr\u003e\n0.0  46.0  3.0  1800  0.0  0.0  6.0  0.0  -  \u003cbr\u003e\n0.25  57.0  26.0  1795  91.5  89.5  57.0  0.0  -  \u003cbr\u003e\n0.5  81.0  50.0  1788  183.0  93.6  78.0  0.0  -  \u003cbr\u003e\n0.75  111.0  74.0  1782  276.0  94.5  84.5  0.0  -  \u003cbr\u003e\n1.0  144.0  99.0  1778  369.0  94.5  87.0  55.0  -  \u003cbr\u003e\n1.15  165.0  114.0  1772  425.0  94.1  87.5  75.0  -  \u003cbr\u003e\n1.25  180.0  125.0  1768  463.0  93.6  87.5  90.0\u003c\/p\u003e","brand":"Industrial Motors","offers":[{"title":"Default Title","offer_id":51648716177730,"sku":"LM80146","price":11111.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0972\/2298\/4002\/files\/lm80177_11.jpg?v=1766395720","url":"https:\/\/industrialmotors.com\/products\/lm80146-125-hp-1800-rpm-405t-fr-dp-230-460-vac-3-ph-rigid-base-lincoln-fire-pump","provider":"Industrial Motors","version":"1.0","type":"link"}