Skip to product information
1 of 1

Industrial Motors

117131.00, 1 HP, 1800 RPM, 56C FR, TEFC, 208-230/460 Vac, 3 PH, Rigid Base, Extreme Duck

117131.00, 1 HP, 1800 RPM, 56C FR, TEFC, 208-230/460 Vac, 3 PH, Rigid Base, Extreme Duck

Regular price $1,679.00
Regular price Sale price $1,679.00
Add to Cart for Discount
Sale Sold out
Shipping calculated at checkout.
$1,679.00 $906.66
Sale
Quantity
Featured Products is no longer manufacturing this motor, possible replacement is the following Featured Products part# 119512

** This motor has been replaced by Model #119512.00 **
117131.00, 1 HP, 1800 RPM, 56C FR, TEFC, 208-230/460 Vac, 3 PH, Rigid Base, Extreme Duck.

Engineering Data
Volts 208-230 Volts 460 Volts 190/380
F.L. Amps 3.1-3 F.L. Amps 1.5 F.L. Amps 2.6/1.3
S. F Amps 3.5-3.3 S. F Amps 1.65 S. F Amps 3/1.5

RPM 1800 Hertz 60/50
HP 1 Duty CONTINUOUS TYPE TN
KW 0.75
Frame 56C Serv. Factor 1.15 Phase 3
Max Amb 40 Design B Code K
Insul Class F Protection NOT Therm.Prot.
Eff 100% 81.5 Eff 75% PF 77
UL Y-(LEESON UL REC) CSA Yes Bearing OPE 6305
CC Number EXEMPT CE Yes Bearing PE 6205
Load Type Inverter Type Speed Range NONE


Motor Wt. 49 LB Enclosure TENV Lubrication POLYREX EM
Nameplate 213-0016 Mounting ROUND Rotation REV
Assembly 042541 Shaft Dia. 5/8 IN Ext. Diag. 005010.52
Cust Part No Outline 028768-700 Ext. Diag2
Packaging B Winding T634253
Carton Label Leeson Stainless Washguard GROUP: 8
Iris Paint VERIFY Test Card 01

Form Factor RMS Amps Const Torque Speed Range
Torque Peak
AB Code Peak@DegC
Resistance
Connection

Rework Status Rework TYPE

Hazardous Loc NONE Brake Motors
Explosion Proof Temp Op Code FORCE
Class GROUP: VDC
Class GROUP: ADC
Brake Coil OHMs @25 C

Performance
Torque UOM FT-LB Inertia (WK²) .135 LB-FT^2
Torque 3(Full Load) 12.1(Break Down) 10.8(Pull Up) 11.3(Locked Rotor)
CURRENT (amps) 1.52(Full Load) 8.87(Break Down) 11.65(Pull Up) 12.03(Locked Rotor)
Efficiency (%) 0(Full Load) 78(75% Load) 77.6(50% Load) 65.8(25% Load)
PowerFactor 0(Full Load) 74(75% Load) 58.8(50% Load) 43.9(25% Load)

Load Curve Data @60/50 Hz, 460 Volts, 1 Horsepower
Load Amps KW RPM Torque EFF PF Rise By Resis Frame Rise
0.0 0.77 0.072 1798 0.0 0.0 11.7 0.0 -
0.25 0.88 0.308 1784 0.8 65.8 43.9 0.0 -
0.5 1.04 0.487 1773 1.5 77.6 58.8 0.0 -
0.75 1.25 0.737 1759 2.3 78.0 74.0 0.0 -
1.0 1.49 0.914 1747 3.0 81.5 77.0 89.8 58.0
1.25 1.76 1.151 1731 3.8 81.2 82.1 0.0 -
1.5 2.04 1.369 1717 4.5 80.2 84.2 0.0

View full details

Attachments