Engineering Data
Volts 208-230 Volts 460 Volts 190/380
F.L. Amps 3.1-3 F.L. Amps 1.5 F.L. Amps 2.6/1.3
S. F Amps 3.5-3.3 S. F Amps 1.65 S. F Amps 3/1.5
RPM 1800 Hertz 60/50
HP 1 Duty CONTINUOUS TYPE TN
KW 0.75
Frame 56C Serv. Factor 1.15 Phase 3
Max Amb 40 Design B Code K
Insul Class F Protection NOT Therm.Prot.
Eff 100% 81.5 Eff 75% PF 77
UL Y-(LEESON UL REC) CSA Yes Bearing OPE 6205
CC Number EXEMPT CE Yes Bearing PE 6205
Load Type Inverter Type Speed Range NONE
Motor Wt. 54.4 LB Enclosure TENV Lubrication POLYREX EM
Nameplate 213-0016 Mounting RIGID Rotation REV
Assembly 042541 Shaft Dia. 5/8 IN Ext. Diag. 005010.52
Cust Part No Outline 028767-700 Ext. Diag2
Packaging B Winding T634253
Carton Label Leeson Stainless Washguard GROUP: 3
Iris Paint VERIFY Test Card 03
Form Factor RMS Amps Const Torque Speed Range
Torque Peak
AB Code Peak@DegC
Resistance
Connection
Rework Status Rework TYPE
Hazardous Loc NONE Brake Motors
Explosion Proof Temp Op Code FORCE
Class GROUP: VDC
Class GROUP: ADC
Brake Coil OHMs @25 C
Performance
Torque UOM LB-FT Inertia (WK²) .135 LB-FT^2
Torque 3(Full Load) 12.1(Break Down) 10.8(Pull Up) 11.3(Locked Rotor)
CURRENT (amps) 1.52(Full Load) 8.87(Break Down) 11.65(Pull Up) 12.03(Locked Rotor)
Efficiency (%) 0(Full Load) 78(75% Load) 77.6(50% Load) 65.8(25% Load)
PowerFactor 0(Full Load) 74(75% Load) 58.8(50% Load) 43.9(25% Load)
Load Curve Data @60/50 Hz, 460 Volts, 1 Horsepower
Load Amps KW RPM Torque EFF PF Rise By Resis Frame Rise
0.0 0.77 0.072 1798 0.0 0.0 11.7 0.0 -
0.25 0.88 0.308 1784 0.8 65.8 43.9 0.0 -
0.5 1.04 0.487 1773 1.5 77.6 58.8 0.0 -
0.75 1.25 0.737 1759 2.3 78.0 74.0 0.0 -
1.0 1.49 0.914 1747 3.0 81.5 77.0 89.8 58.0
1.25 1.76 1.151 1731 3.8 81.2 82.1 0.0 -
1.5 2.04 1.369 1717 4.5 80.2 84.2 0.0 -
1.75 2.35 1.607 1701 5.3 78.9 85.8 0.0 -
2.0 2.67 1.843 1683 6.0 77.8 86.7 0.0 -