Industrial Motors
Couldn't load pickup availability
171801.60, 125 Hp, 1200 Rpm, 445T FR, TEFC, 460 Vac, 3 PH, Rigid Base, Wattsaver, Severe Duty Motor.
Engineering Data
Volts 460 Volts Volts 380
F.L. Amps 155 F.L. Amps F.L. Amps 150
S. F Amps 175 S. F Amps S. F Amps 170
RPM 1200 Hertz 60/50
HP 125 Duty CONTINUOUS TYPE TW
KW 93
Frame 445T Serv. Factor 1.15 Phase 3
Max Amb 40 Design B Code G
Insul Class F Protection NOT Therm.Prot.
Eff 100% 95.4 Eff 75% PF 79
UL Y-(LEESON UL REC) CSA Yes Bearing OPE 6317
CC Number CC005A CE Yes Bearing PE 6318
Load Type Inverter Type Speed Range NONE
Motor Wt. 1596 LB Enclosure TEFC Lubrication POLYREX EM
Nameplate 93458-F-LN-FHKLR-L-C-D Mounting RIGID Rotation REV
Assembly Shaft Dia. Ext. Diag. 00519001
Cust Part No Outline 16954760 Ext. Diag2
Packaging N Outline Dash No Winding T22806005
Carton Label GROUP : 1
Iris Paint GREEN (EPOXY) Test Card
Form Factor RMS Amps Const Torque Speed Range
Torque Peak
AB Code Peak@DegC
Resistance
Connection
Rework Status Rework TYPE
Hazardous Loc DIVISION 2 Brake Motors
Explosion Proof Temp Op Code FORCE
Class GROUP : VDC
Class GROUP : ADC
Brake Coil OHMs @25 C
Performance
Torque UOM Inertia (WK²)
Torque
CURRENT (amps)
Efficiency (%)
PowerFactor
Load Curve Data @60/50 Hz , 380 Volts , 125 Horsepower
Load Amps KW2 RPM Torque EFF PF Rise By Resis Frame Rise
0.0 62.0 3.1 1200 0.0 0.0 3.5 0.0 -
0.25 73.5 25.4 1198 137.0 91.7 43.0 0.0 -
0.5 95.0 49.5 1196 274.0 94.5 65.0 0.0 -
0.75 123.0 73.5 1194 412.0 95.4 75.0 0.0 -
1.0 155.0 97.5 1192 551.0 95.4 79.0 70.0 -
1.15 175.0 112.0 1190 634.0 95.4 80.0 90.0 -
1.25 191.0 123.0 1188 691.0 95.0 80.5 0.0 -