Industrial Motors
Couldn't load pickup availability
Engineering Data
Volts 460 Volts Volts 380
F.L. Amps 227 F.L. Amps F.L. Amps 205
S. F Amps 261 S. F Amps S. F Amps
--------------------------------------------------------------------------------
RPM 1800 Hertz 60/50
HP 200 Duty CONTINUOUS TYPE TFR
KW 149
Frame 445TS Serv. Factor 1.15 Phase 3
Max Amb 40 Design B Code G
Insul Class F Protection NOT Therm.Prot.
Eff 100% 96.2 Eff 75% PF 86
UL V-INS, CONST UL REC CSA Yes Bearing OPE 6315
CC Number CC004A CE Yes Bearing PE 6318
Load Type Inverter Type Speed Range NONE
--------------------------------------------------------------------------------
Motor Wt. 1566 LB Enclosure TEFC Lubrication STANDARD
Nameplate 3B451-AZ-X-BCDLM-D-A-X Mounting RIGID Rotation REV
Assembly Shaft Dia. Ext. Diag. A-EE7340-LN
Cust Part No Outline B-XK2F1SS2-2317 Ext. Diag2
Packaging B Outline Dash No Winding L4454005
Carton Label GROUP: 1
Iris Paint STANDARD Test Card
--------------------------------------------------------------------------------
Form Factor RMS Amps Const Torque Speed Range
Torque Peak
AB Code Peak@DegC
Resistance
Connection
--------------------------------------------------------------------------------
Rework Status Rework TYPE
--------------------------------------------------------------------------------
Hazardous Loc NONE Brake Motors
Explosion Proof Temp Op Code FORCE
Class GROUP: VDC
Class GROUP: ADC
Brake Coil OHMs @25 C
Performance
Torque UOM Inertia (WK²)
Torque
CURRENT (amps)
Efficiency (%)
PowerFactor
Load Curve Data @60/50 Hz, 460 Volts, 200 Horsepower
Load Amps KW RPM Torque Eff PF Rise By Resis Frame Rise
0.0 70.0 3.2 1800 0.0 0.0 5.5 0.0 -
0.25 89.5 41.0 1797 146.0 90.2 57.5 0.0 -
0.5 128.0 79.0 1795 293.0 95.0 77.0 0.0 -
0.75 175.0 117.0 1790 440.0 95.4 84.0 0.0 -
1.0 227.0 156.0 1788 587.0 96.2 86.0 60.0 -
1.15 261.0 179.0 1785 677.0 95.8 86.0 80.0 -
1.25 284.0 195.0 1783 736.0 95.4 86.0 95.0